Hawke PL612 Enclosure Populated As A Standard Offering. Cable Systems supply Cable Glands and other electrical products including Hawke EExe certified junction boxes to suit the customers requirements whilst still retaining certification. This is endorsed and backed by Hawke Cable Glands Limited, which offers customers a fast lane service for this product. This service is also available on industrial enclosures. In doing this, we have had to obtain certification by the Electrical Equipment Certification Service (EECS) for the Stockist Assembler Scheme. This was attained in 1994 and allows ourselves to issue our own Licence with the BASEEFA certificate.
Cable Systems Limited sales@cablesystems.co.uk

Hawke InternationalHawke

Enclosures Dissipated Wattage


Enclosure Dissapated Wattage
Enclosure Type Temperature Class
T6 40°C & T5 55°C T6 55°C T5 40°C T6 65°C T5 65°C
PL612 GRP 4.1 2.5 5.6 1.5 3
PL615 GRP 6.4 4 8.8 2.4 4.8
PL620 GRP 11.4 7.1 15.6 4.2 8.5
PL626 GRP 11.4 7.1 15.6 4.2 8.5
PL630 GRP 20.8 13 28.6 7.8 15.6
PL712 GRP 3.352 2.148 4.6 1.2 2.4
PL722 GRP 5.318 3.323 7.3 1.9 3.9
Size 1 Stainless Steel 13.95 8.7 19.1 5.2 10.4
Size 2 Stainless Steel 18.15 11.3 24.9 6.8 13.6
Size 3 Stainless Steel 23.7 14.8 32.5 8.8 17.7
Size 4 Stainless Steel 29.95 18.7 41.1 11.2 22.4
Size 5 Stainless Steel 32.85 20.5 45.1 12.3 24.6
Size 6 Stainless Steel 40 25 55 15 30
Size 7 Stainless Steel 52 23.5 71.5 19.5 39
Size 8 Stainless Steel 65 40.6 89.3 24.3 48.7
Size 9 Stainless Steel 79.35 49.5 109.1 29.7 59.5

Dissipated Wattage Factor

The Dissipated Wattage Factor of the Enclosures has been established by test to ensure that the maximum temperature as permitted by temperature certification is not exceeded. When terminal quantities greater than those at maximum amps are required (up to maximum physical quantity only) then the current shall be reduced accordingly to remain within the Dissipated Wattage Factor of the Enclosure.


Combined Terminal Resistance Factor

This factor is used to determine the number of terminals that can be accommodated within the Enclosure without exceeding the Wattage Factor. The Combined Terminal Resistance Factor is the sum of the individual terminal resistance's and the resistance of the cable core equal in length to the Enclosure maximum diagonal. (Core Resistance is taken from BS6360).Combined terminal resistance factor.


Wattage to be Dissipated = N x F x I²

N = Number of Terminals. F = Combined Terminal Resistance Factor. I = Maximum Current.

e.g. Number of terminals in a PL630 Enclosure at 20.8 Watts - 10 x 'WDU 2.5' (1=21A), 2 x 'WDU 6' (1=36A), (10 x 0.00290465 x 21² = 12.9) + (2 x 0.0012142 x 36² = 3.2 Watts). Total Watts = 12.9 + 3.2 = 16.1 Watts.


Therefore this terminal combination is acceptable as the wattage is less than that of the PL630 maximum Watts of 20.8W.


Note - If a smaller than maximum permitted conductor is fitted into a power terminal, then the smaller conductor resistance must be used when calculating the combined terminal resistance.


Transposed Formula

wattage equation

Enclosures dissipated wattage data sheet.



Hawke Cable Glands | Hawke Enclosures | Hawke EX Connectors | Hawke Adaptors & Reducers

Hawke Transformer Breathers | Hawke Accessories


 

Contact the Cable Systems Ltd sales office for further details and prices.

Tel: (01925) 852745

Fax: (01925) 820803

Email: sales@cablesystems.co.uk

Ex-Mo - the NEW Hazardous Area Motion Sensor

Recent News

Our sister company JK Electrical has recently launched a new website. JK Electrical are specialist suppliers of Telemecanique products.

Get your FREE Hazardous Area Wallchart
Get the NEW Cable Systems Brochure
We accept the following Credit Cards
LRQA ISO Certification

Hours of Business
Monday-Thursday 8am-5pm Friday 8am-3pm

Cable Systems Ltd, 2-6 Gawsworth Court, Risley Road, Birchwood, Warrington, Cheshire, WA3 6NJ
T: 01925 852745  F: 01925 820803  Email: sales@cablesystems.co.uk