Unistrut
Basket Tray Loading Information

Load test according CEI/IEC 61537:2001
Q = UDL (uniformly distributed load)
Safety Factor = 1.7
L = intermediate span
F = deflection = 1/100 of the intermediate span (max.)
S = splice location
Stated loadings apply to mild steel product only.
Unistrut’s load testing is in accordance with CEI/IEC 61537:2001. In practical terms this covers continuous/multi span installations, evenly loaded along the length of, and across the full width of the basket. The end spans in these installations should be reduced to 0.75 of the intermediate spans.
DEFLECTION: Unistrut’s load and deflection figures are in accordance with CEI/IEC 61537:2001, with the characteristic deflection of Unistrut Cable Basket limited to span/100. and load figures inclusive of a safety factor of 1.7. ACCESSORIES: To ensure adequate support, accessories should be supported locally.
COUPLERS: The loading and deflection tables for Unistrut Cable Basket assume that the couplers are located at L/5 as shown on the schematic above. Couplers should not be located in end spans or over support locations and only one pair of couplers should be installed per span. A factor of 0.7 must be applied to the loading figures when couplers are not positioned at L/5.
| Width (mm) |
Useful Cross Section (cm2) | |
| AF2 | AF3 | |
| 50 | 25.0 | - |
| 100 | 50.1 | 96.1 |
| 150 | 75.1 | - |
| 200 | 100.2 | 192.2 |
| 300 | 150.3 | 288.3 |
| 400 | 198.4 | 382.4 |
| 450 | 221.4 | - |
| 500 | 246.0 | 476.0 |
| 600 | 295.2 | - |
Unistrut Support Systems | Unistrut Cable Ladder | Unistrut Basket Tray | Unistrut Cable Tray | Unistrut Pipe Clips
Contact the Cable Systems Ltd sales office for further details and prices.
Tel: (01925) 852745
Fax: (01925) 820803
Email: sales@cablesystems.co.uk
Recent News
Our sister company JK Electrical has recently launched a new website. JK Electrical are specialist suppliers of Telemecanique products.