EZE-22 Enclosure. Cable Systems supply Cable Glands and other electrical products including Hawke EExe certified junction boxes to suit the customers requirements whilst still retaining certification. This is endorsed and backed by Hawke Cable Glands Limited, which offers customers a fast lane service for this product. This service is also available on industrial enclosures. In doing this, we have had to obtain certification by the Electrical Equipment Certification Service (EECS) for the Stockist Assembler Scheme. This was attained in 1994 and allows ourselves to issue our own Licence with the BASEEFA certificate.
Cable Systems Limited sales@cablesystems.co.uk

Hawke InternationalHawke

EZE-22 Enclosure


EZE-22   EZE-42   EZE-62


EZE-22 Enclosure

Technical Data

Increased Safety Exe. EXe Logo II 2 GD Exe II
Baseefa Certificate No. Baseefa04ATEX0171X.
Baseefa Certificate No. Baseefa04ATEX0170U.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Construction and test standards EN 50014, EN 50019 and EN 50281-1-1. IEC 60079-0 and IEC 60079-7.
IP66 ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection witnessed by Baseefa 2001.
Operating temperature range -40°C to +80°C.
Temperature class and ambient T6 40°C.
Optional T5 with ambients up to 65°C.


EZE-22 Enclosure Dimensions


Maximun Quantity of Entries per Face
Thread Size M16 M20/Os/O M20/A M25 M32 M40 M50
Bottom Face Quantity 20 20 14 (12*) 9 (8*) 6 4 2

* Recommended maximum for Cable Gland installation.


Terminal Capacity Data
Terminal Type Conductor Size (mm²) Max.
Volts
Typical Terminal Arrangements
1 Vertical Rail
(Max. Physical)
1 Vertical Rail
(Max. Current)
2 Vertical Rail *
(Max. Physical)
Min. Max. Terminal
Quantity
Current
(Amps)
Terminal
Quantity
Current
(Amps)
Terminal
Quantity
Current
(Amps)
WDU 2.5N 0.5 2.5 420 38 11 12 21 76 8
WDU 2.5 0.5 2.5 550 38 12 12 21 76 8
WDU 4 0.5 4 750 32 16 11 28 64 11
WDU 6 0.5 6 550 24 23 10 36 - -
WDU 10 1.5 10 550 19 33 8 50 - -
WDU 16 1.5 16 750 16 46 7 66 - -
WDU 35 2.5 35 750 12 78 6 109 - -
Information in the above table is based on the maximum conductor size permitted for the terminal.
If earth terminals are required, the quantity should be taken from the maximum physical terminal quantity.
* Special box arrangement with rail heights staggered.

Notes:

  1. A combination of different sized entries is possible, please contact Cable Systems Ltd for more information.

  2. The table above gives an indication of potential terminal arrangements. Please contact Hawke for information on other arrangements or empty Enclosures.

  3. A combination of different sized terminals is possible, please contact Cable Systems Ltd for more information.

  4. Other terminal types are available.


Hawke Cable Glands | Hawke Enclosures | Hawke EX Connectors | Hawke Adaptors & Reducers

Hawke Transformer Breathers | Hawke Accessories


 

Contact the Cable Systems Ltd sales office for further details and prices.

Tel: (01925) 852745

Fax: (01925) 820803

Email: sales@cablesystems.co.uk

Get your FREE 2010 Year Planner Wallchart
Get your FREE Hazardous Area Wallchart
We accept the following Credit Cards
LRQA ISO Certification

Hours of Business
Monday-Thursday 8am-5pm Friday 8am-3pm

Cable Systems Ltd, 2-6 Gawsworth Court, Risley Road, Birchwood, Warrington, Cheshire, WA3 6NJ
T: 01925 852745  F: 01925 820803  Email: sales@cablesystems.co.uk