Hawke
Hazardous Area Cable Glands
501/414
501/414 | 501/421| 501/423 | 501/453/RAC | 501/453/RAC/L | 501/453/Universal | CSB 656 | ICG 623
ICG 653/Universal | ICG 653/Universal/L | PSG 553/RAC | SB 474 | Oversize Cable Glands

Application
Outdoor or Indoor use.
For use with non-armoured elastomer and plastic insulated cables installed in conduit.
Features
Provides a cable retention seal onto the cables outer sheath.
When used in increased safety applications, this cable gland may be used with braided cable where the braid and the cables outer sheath pass into the enclosure. The braid must be suitably terminated into the enclosure.
Provides female running coupler for cable gland or conduit entry.
Materials & Finishes
The 501/414 Cable Gland is manufactured as standard in Brass, Stainless Steel and Aluminium.
NPT entries are nickel plated as standard.
Full nickel plating by electroplating or electroless plating is also available, as are other materials on request.
Technical Data
Flameproof Exd and Increased Safety Exe
II 2 GD
Baseefa Certificate No. BAS01ATEX2076X.
The above certificate is still current, however it is to be superseded by:
Baseefa Certificate No. Baseefa06ATEX0056X.
IECEx Certificate No. IECEx BAS 06.0013X.
Suitable for use in Zone 1, Zone 2, Zone 21 and Zone 22.
Suitable for use in Gas Groups IIA, IIB and IIC.
Construction and test standards EN 50014,EN 50018, EN 50019 and EN 50281-1-1. IEC 60079-0, IEC 60079-1 and IEC 60079-7.
IP 66, IP67 and IP68 (30 metres for 7 days) ingress protection to IEC 60529 and EN 60529.
DTS01 deluge protection certified by ITS.
Operating temperature range -60°C to +100°C as standard.
Alternative certification options available:
Option available, Exd IIC, Exe II. Certificate No. 1015065 (LR 78713-7).

| Cable Gland Selection | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Size Ref. |
Male Entry Thread Size |
Female Entry Thread Size |
Cable Acceptance Details | ‘G’ Compressed Length |
Hexagon Dimensions |
|||||||
| Outer Sheath ‘B’ | ||||||||||||
| Metric | NPT * |
Metric | NPT # |
Standard Seal |
Alternative (S) Seal |
Across Flats |
Across Corners |
|||||
| Standard | Option | Min. | Max. | Min. | Max. | |||||||
| A | M20 | ¾" | ½" | M20 | - | 11.0 | 14.3 | 8.5 | 13.4 | 63.9 | 30.0 | 34.6 |
| B | M25 | 1" | ¾" | M25 | - | 13.0 | 20.2 | 9.5 | 15.4 | 52.8 | 36.0 | 41.6 |
| C | M32 | 1¼" | 1" | M32 | - | 19.0 | 26.5 | 15.5 | 21.2 | 69.5 | 46.0 | 53.1 |
| C2 | M40 | 1½" | 1¼" | M40 | - | 25.0 | 32.5 | 22.0 | 28.0 | 72.3 | 55.0 | 63.5 |
| D | M50 | 2" | 1½" | M50 | - | 31.5 | 44.4/42.3 † | 27.5 | 34.8 | 92.8 | 65.0 | 75.1 |
| E | M63 | 2½" | 2" | M63 | - | 42.5 | 56.3/54.3 † | 39.0 | 46.5 | 93.2 | 80.0 | 92.4 |
| F | M75 | 3" | 2½" | M75 | - | 54.5 | 68.2/65.3 † | 48.5 | 58.3 | 94.9 | 95.0 | 109.6 |
| † Smaller value is applicable when selecting the option NPT entry thread. All metric entry threads are 1.5mm pitch medium fit. All dimensions in millimetres (except * ). # NPT female thread sizes equivalent to those shown in the table for the male thread size are available. Hexagon dimensions as shown may alter. |
||||||||||||
Cable Gland Ordering Examples
Type/Size/Male Thread/Female Thread
e.g. 501/414/C/M32/M32
501/414/C/1¼" NPT/M32
Cable Gland with Alternative Seal (S)
e.g. 501/414/C/M32/M32/S
501/414/C/1¼" NPT/M32/S
Hawke Cable Glands | Hawke Enclosures | Hawke EX Connectors | Hawke Adaptors & Reducers
Hawke Transformer Breathers | Hawke Accessories
Contact the Cable Systems Ltd sales office for further details and prices.
Tel: (01925) 852745
Fax: (01925) 820803
Email: sales@cablesystems.co.uk
Recent News
Our sister company JK Electrical has recently launched a new website. JK Electrical are specialist suppliers of Telemecanique products.