Hawke Industrial Cable Gland 153/RAC (Type E1W, E1X and E1Z). Cable Systems supply Cable Glands and other electrical products including Hawke EExe certified junction boxes to suit the customers requirements whilst still retaining certification. This is endorsed and backed by Hawke Cable Glands Limited, which offers customers a fast lane service for this product. This service is also available on industrial enclosures. In doing this, we have had to obtain certification by the Electrical Equipment Certification Service (EECS) for the Stockist Assembler Scheme. This was attained in 1994 and allows ourselves to issue our own Licence with the BASEEFA certificate.
Cable Systems Limited sales@cablesystems.co.uk

Hawke InternationalHawke

Industrial Cable Gland 153/RAC/L (Type E2W, E2X and E2Z)


Industrial Cable Gland 114 | Industrial Cable Gland 121 (Type A2) | Industrial Cable Gland 123 (Type A2)

Industrial Cable Gland 150/RAC (Type BW, BX and BZ) | Industrial Cable Gland 151/RAC (Type CW, CX and CZ)

Industrial Cable Gland 153/RAC (Type E1W, E1X and E1Z) | Industrial Cable Gland 153/RAC/L (Type E2W, E2X and E2Z)

Industrial Cable Gland 153/Universal (Type E1W, E1X and E1Z)


Industrial Cable Gland 153/RAC/L (Type E2W, E2X and E2Z)

Application

Outdoor or Indoor use.
For use with single wire armoured ‘W’ wire braided ‘X’ and steel tape armoured ‘Z’ elastomer and plastic insulated cables with a lead inner sheath.


Features

Provides armour clamping using one clamping arrangement for all armour/braid types.
Provides a seal and an electrical bond on the cables lead inner sheath.
Deluge protection option available.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer sheath.


Materials & Finishes

The 153/RAC/L Cable Gland is manufactured as standard in Brass, Stainless Steel and Aluminium.
NPT entries are nickel plated as standard.
Full nickel plating by electroplating or electroless plating is also available, as are other materials on request.

Technical Data

Construction and test standards EN 50262. BS 6121 Part 1. Type E2W, E2X and E2Z.
IP66, IP67 and IP68 (30 metres for 7 days) ingress protection to IEC 60529, EN 60529 and NEMA 4X.
Operating temperature range -60°C to +80°C as standard.

Dimensions Industrial Cable Gland 153/RAC/L (Type E2W, E2X and E2Z)



Cable Gland Selection
Size
Ref.
Entry Thread
Size
‘H’
Thread
Length
Cable Acceptance Details ‘G’
Compressed
Length
Hexagon
Dimensions
‘A’ Inner Lead Sheath ‘B’
Outer Sheath
‘C’
Armour/Braid
Metric NPT
*
Standard
Seal+Bond
Alternative
Seal+Bond
Across
Flats
Across
Corners
Standard Option Min. Max. Min. Max. Min. Max. Orientation
1
Orientation
2
O M20 ‡ ½" - 15 6.5 10.5 4.0 8.0 9.5 16.0 0.9 / 1.25 0 / 0.7 65.1 24.0 27.7
A M20 ¾" ½" 15 - - 8.5 13.0 12.5 20.5 0.9 / 1.25 0 / 0.7 66.1 30.0 34.6
B M25 1" ¾" 15 12.5 19.0 9.5 15.4 16.9 26.0 1.25 / 1.6 0 / 0.7 71.4 36.0 41.6
C M32 1¼" 1" 15 19.0 25.0 14.5 21.2 22.0 33.0 1.6 / 2.0 0 / 0.7 75.2 46.0 53.1
C2 M40 1½" 1¼" 15 25.0 31.2 22.0 28.0 28.0 41.0 1.6 / 2.0 0 / 0.7 77.1 55.0 63.5
D M50 2" 1½" 15 31.5 42.3/42.8 † 27.5 34.8 36.0 52.6 1.8 / 2.5 0 / 1.0 90.3 65.0 75.1
E M63 2½" 2" 15 42.0 53.3/54.5 † 39.0 46.5 46.0 65.3 1.8 / 2.5 0 / 1.0 96.7 80.0 92.4
F M75 3" 2½" 15 54.5 66.0/64.3 † 48.5 58.3 57.0 78.0 1.8 / 2.5 0 / 1.0 96.0 95.0 109.6

Larger Cable Glands available in 153/L design as shown below. More details on larger Cable Glands.

G M80 3½" - 20 67.0 70.0 - - 75.0 89.5 # # 95.6 106.4 123.0
H M90 3½" - 20 67.0 75.0 - - 75.0 89.5 # # 95.6 115.0 132.8
J M100 4" - 20 75.0 89.5 - - 88.0 104.5 # # 95.6 127.0 146.7
† Smaller value is applicable when selecting the option NPT entry thread.
‡ Size O is available with an M16 thread size. For O size with M16 thread, the maximum cable inner sheath diameter is 10.9mm.
O - F size metric entry threads are 1.5mm pitch as standard. For G size Cable Glands and above, a 2mm pitch is supplied as standard (1.5mm pitch with 15mm length of thread can be supplied) please specifiy when ordering.
All dimensions in millimetres (except*).

Alternative Reversible Armour Clamping Ring (RAC)

Selection Table
Size Ref. Steel Wire Armour/Braid/Tape
Orientation 1 Orientation 2
O/Os 0.8 / 1.0 0.4 / 0.8
A 0.8 / 1.0 0.4 / 0.8
B 0.9 / 1.25 0.4 / 0.8
C 1.2 / 1.6 0.6 / 1.2
C2 1.2 / 1.6 0.6 / 1.2
D 1.45 / 1.8 1.0 / 1.45
E 1.45 / 1.8 1.0 / 1.45
F 1.45 / 1.8 1.0 / 1.45

Cable Gland Ordering Examples

e.g. 153/RAC/C/M32/L
153/RAC/C/1¼" NPT/L


Cable Gland with Alternative Seal (S)

e.g. 153/RAC/C/M32/K
153/RAC/C/1¼" NPT/K


Cable Gland With Alternative Clamping Ring

e.g. 153/RAC/C/M32/L/AR
153/RAC/C/1¼" NPT/L/AR



Hawke Cable Glands | Hawke Enclosures | Hawke EX Connectors | Hawke Adaptors & Reducers

Hawke Transformer Breathers | Hawke Accessories


 

Contact the Cable Systems Ltd sales office for further details and prices.

Tel: (01925) 852745

Fax: (01925) 820803

Email: sales@cablesystems.co.uk

Get your FREE 2010 Year Planner Wallchart
Get your FREE Hazardous Area Wallchart
We accept the following Credit Cards
LRQA ISO Certification

Hours of Business
Monday-Thursday 8am-5pm Friday 8am-3pm

Cable Systems Ltd, 2-6 Gawsworth Court, Risley Road, Birchwood, Warrington, Cheshire, WA3 6NJ
T: 01925 852745  F: 01925 820803  Email: sales@cablesystems.co.uk