Victor
Flourescent Lighting - VL104C Em Ex e Emergency (Recessible) - Zone 1
Flourscent Bulkhead Pendant Floodlight Heli Deck Wellglass | Zone 1 Zone 2 Industrial

Applications
The VL104C Em has the same features as the VL104C and can provide emergency illunination in the event of a power failure. Emergency operation provides up to 90 minutes of lighing from the internal battery.
The VL104C Em has a battery management system that monitors and self tests the battery to ensure optimum performance.
The Em version also has options for modular tiled and non-modular ceilings with a range of lamp combinations:
• 2 x 18W
• 4 x 18W
• 2 x 36W
• 3 x 36W
• 4 x 36W
Please contact our Technical Department for details on the appropriate options to match your ceiling type: sales@cablesystems.co.uk
Specifications
Type of Protection: |
Ex eqm (Increased Safety Powder Filling Encapsulation) Dust Protected Enclosure |
ATEX Classification: |
Group II Category 2 G D |
Area Classification: |
Zone 1 and Zone 21 areas to EN 60079-10 and EN 50281-3 with installation to EN 60079-14 and EN 50281-1-2 |
| Apparatus Standard: | EN 50014, EN 50017, EN 50019, EN 50028 |
Certificate: |
Baseefa05ATEX0237X |
Coding: |
Ex II 2 G D EEx eqm II T4 |
Enclosure: |
White polyester painted zinc coated steel body and frame Silicone rubber gasket. Prismatic polycarbonate diffuser |
| Reflector/Geartray: | White polyester painted zinc coated steel |
Entry: |
3 x 20mm diameter holes for cable entries, 2 at one end and 2 at the other end |
Termination: |
4 core 6mm max. conductor with looping and through wiring 16A rating |
Installation: |
Fixed side brackets with swing out arms with provision for drop rod mounting |
| Lampholder: | G13 (Bi-pin) |
Lamp Type: |
T8 tubular fluorescent |
Control Gear: |
High Frequency |
Relamping: |
Access via front cover secured by screws |
| Burning Position: | Horizontal |
| Ingress Protection: | IP65 to EN 60598-1:2000. Satisfies the requirements of FS 209D Class 100 Clean Rooms ISO Standard 1997 Class 5 |
| Electrical Supply: | 220V-254V 50/60Hz 220V-300V dc non-emergency only |
| Duration: | 3 hours or 90 minutes for high emergency output version (HEO) |
| Emergency Output: | 30% of one lamp (18W) |